Crestron CHV-TSTAT and CHV-THSTAT Thermostats
Operations and Installation Guide DOC. 8163E Thermostats: CHV-TSTAT and CHV-THSTAT
51
Slab 4B – 2-Stage Heat/1-Stage Cool with Slab Maximum (Heat
Pump)
Press and hold the MODE and VIEW buttons simultaneously for 5 seconds to enter setup mode.
SETUP: SYSTEM
SETUP: SYSTEM
Heat Sys Type:
Slab MAX T:
HP/AUX or DF:
SLAB 4B
122
o
HP/Aux
2 STG SPACE HEAT - 1 STG
COOL WITH SLAB MAX (HP)
SLAB = W1, HT/CL = Y1/O/G
Press To Continue
Heat Sys Type: SLAB 4B
Slab MAX T: Select 39°122° F (39° 50° C). Used to
prevent the floor from becoming too hot on long heat calls.
HP/Aux or DF: Dual fuel runs either the heat pump or the
aux output, depending on outdoor temperature. The heat
pump with aux can stage the heat when required to improve
performance.
Dual Fuel: A dual fuel system combines an energy
efficient air source heat pump with a new or existing oil,
gas or propane furnace. The furnace runs in place of the
heat pump in cold weather.
Aux (Auxiliary) Heat: When the heat pump can no
longer efficiently transfer heat from the outside air, the
thermostat automatically turns on a secondary heat
source, such as electric resistive heat.
NOTE: Slab mode 4B requires an air temperature source
and a slab remote sensor (CHV-RSS).
SETUP: SYSTEM PERFORMANCE
SETUP: SYSTEM PERF
Heat Anticipator:
Cool Anticipator:
Intrstg Differential:
HP Balance Pt:
AUX Balance Pt:
5
6
0.5
0
Off
1
0
Press To Continue
Heat Anticipator and Cool Anticipator: Select 16.
Low number = more frequent cycles, faster response.
High number = less frequent cycles, slower response.
Intrstg Differential: Select 0.5º 8.0º F.
The proportional temperature error to trigger the second
stage.
HP Balance Pt: Select 90º F or N/A. Minimum outdoor
temperature at which the heat pump runs (requires an
outdoor temperature sensor).
AUX Balance Pt: Select 90º F or N/A. Maximum
outdoor temperature at which Aux heat system supplements
the heat pump (requires an outdoor temperature sensor).