Thermostats Crestron CHV-TSTAT and CHV-THSTAT
26
Thermostats: CHV-TSTAT and CHV-THSTAT Operations and Installation Guide DOC. 8163E
3. Slab Systems Definitions
Slab heating works from the ground up. The heating components are
installed below the floor or are embedded in a concrete slab. Heat radiates
from the floor to warm the space above. The CHV-TSTAT and
CHV-THSTAT support seven variations of slab heat systems.
SLAB 1: Floor warming only. Operates the slab heat to maintain a
particular slab temperature. System mode is enabled/disabled with Floor
Warming Heat and OFF inputs. Slab is maintained at the slab setpoint
temperature value. Connection to the slab output relay is terminal W1.
Refer toSlab 1 Floor Warming Onlywhich starts on page 35.
SLAB 2: 1-stage space heat with slab maximum. Maintains a particular air
temperature using the slab to heat the space. Does not heat over the slab
maximum temperature even if this results in the space being under-heated.
Connection to the slab output relay is terminal W1. Refer toSlab 2 – 1-
Stage Space Heat with Slab Maximum” which starts on page 39.
SLAB 3: 1-stage space heat with slab maximum and slab minimum.
Performs the same operation as SLAB 2, and also keeps the slab at least as
warm as slab setpoint. This may result in the space being overheated to
maintain the slab minimum temperature. Connection to the slab output relay
is terminal W1. Refer toSlab 3 – 1-Stage Heat with Slab
Minimum/Maximumwhich starts on page 43.
SLAB 4A: 2-stage space heat with slab maximum and 1-stage cool.
Maintains the air temperature using the slab for heat, up to the slab
maximum. Augments the air heating by using a second stage of heat
(generally a forced air system). Allows the second stage to operate by itself
should the slab reach is maximum temperature and shut off. Cools the
space with cooling call. Intended for heat-cool type forced air systems, with
relay output connections to terminal W1 for slab, terminal W2 for second
stage heat, and terminal Y1 for cooling. Refer to “Slab 4A 2-Stage
Heat/1-Stage Cool with Slab Maximum” which starts on page 47.
SLAB 4B: Same operation as SLAB4A, but intended for a heat pump type
second stage. Relay output connections are terminal W1 for slab heat, with
heat pump-type connections on terminals Y1/O/G for cooling and heating
calls. Aux heat is on terminal W2. Refer toSlab 4B – 2-Stage Heat/
1-Stage Cool with Slab Maximum (Heat Pump)” which starts on page 51.
SLAB 5A: 1-stage space heat and cool with floor warming. Combines the
operation of a space heating/cooling thermostat with a floor-warming
thermostat. Maintains the slab at slab setpoint, and maintains the space at
the heat, cool, or auto setpoints. Systems effectively operate independently.
Heat/Cool/Auto/Off sets the space control modes, and Floor Warming
HEAT/OFF sets the slab mode. Intended for heat-cool style systems, with
slab connection on terminal W1, space heat on terminal W2, and space cool
on terminal Y1. Refer toSlab 5A – 1-Stage Heat/Cool with Floor
Warming” which starts on page 55.
SLAB 5B: Same as SLAB5A, but for heat pump space systems, with slab
heat on terminal W1, and space heat/cool on terminals Y1/O/G. Aux heat is
on terminal W2. Refer to “Slab 5B – 1-Stage Heat/Cool with Floor
Warming (Heat Pump)” which starts on page 59.