Thermostats Crestron CHV-TSTAT and CHV-THSTAT
22
Thermostats: CHV-TSTAT and CHV-THSTAT Operations and Installation Guide DOC. 8163E
Installation
The location of the thermostat can affect its performance and efficiency. Install the
thermostat away from direct sunlight, drafts, doorways, skylights, and windows.
Also make sure the thermostat is conveniently located for programming, and do not
mount on an exterior wall. The thermostats may be mounted directly to drywall or to
a 1-gang box.
Thermostats and sensors are mounted 60 inches (~1.6 meters) above the finished
floor (HVAC industry standard).
The following tools and hardware are required for installation.
Phillips screwdriver (not supplied)
Two 6-32 x 1-inch panhead screws (included) for mounting to a 1-gang box
1-gang electrical box (not supplied)
Wall anchors (not supplied) and screws (not supplied) for mounting directly
to drywall
Refer to the following illustrations and use the following procedure to install the
CHV-TSTAT or the CHV-THSTAT.
NOTE: When installing directly on drywall, use anchoring screws and hardware.
Make sure the back of the thermostat is flush with drywall and the unit is level.
NOTE: If replacing an existing thermostat, make note of the wire colors and
positions before removing the old thermostat.
1. Separate thermostat front plate from back plate (it may be necessary to exert
force when removing the faceplate).
2. Turn off the circuit breaker when connecting power to the thermostat, and
connect wiring as required (wiring goes through center hole on back plate).
NOTE: Ensure the correct position of the P4 jumper; refer to pages 11
through 20.
3. Attach back plate to drywall with screws and anchors (anchor hardware not
supplied) 60 inches (~1.6 meters) above the finished floor. Thermostat may
also be mounted to a 1-gang electrical box, horizontally mounted, using the
two included 6-32 x 1 inch panhead screws. If using a 5-sided
1-gang electrical box, fill with insulation material to minimize wall air
ingress. Ensure that the thermostat is level and the ventilation holes in the
backplate are not blocked.
4. Note orientation of front plate connection leads and reattach the front plate
to the back plate (make sure front plate snaps in place and no wires are
pinched).
CAUTION: Do not press on the LCD display during installation, as this
may cause the screen to crack.
5. Carefully remove the warning label from the LCD display.