Crestron CHV-TSTATEX-FCU infiNET EX Thermostat (Fan Coil Unit)
Operations & Installation Guide DOC. 7206C infiNET EX Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU
3
Remote Sensors
Optional remote temperature sensors can be connected to the CHV-TSTATEX for
enhanced flexibility and optimized performance. Climate can be regulated according
to an average of multiple sensors, or the built-in sensors can be disabled entirely to
allow the CHV-TSTATEX to be installed out of view. For heat pump-type systems,
outdoor temperature can be monitored to optimize system performance. Compatible
sensors include the CHV-RTS and the CHV-RSS (both sold separately).
Specifications
Specifications for the CHV-TSTATEX-FCU are listed in the following table.
CHV-TSTATEX-FCU Specifications
SPECIFICATION DETAILS
Wireless
RF Transceiver 2-way RF, 2.4 GHz ISM Channels 11-26 (2400
to 2483.6 MHz), IEEE 802.15.4 compliant
Range (typical) 150 ft (46 m) indoor, 250 ft (76 m) outdoor;
Subject to site-specific conditions;
range is increased by adding additional
devices or CLW-EXPEX wireless expander
(sold separately)
Gateway Requires a CEN-RFGW-EX RF gateway or
MC3 3-Series Control System
®
(both sold
separately)
Display Backlit LCD with two large 7-segment digits,
two small 7-segment digits, 14 dedicated
symbols;
Displays ambient temperature, setpoint,
system mode, fan setting, call activity, low
battery, RF or control system communication
errors, firmware download progress, setup
parameter/function and value
Measurement Range
Ambient Temperature -10º to 110º F (-23º to 43º C)
Display Limits -9º to 99º F (-9º to 43º C)
Temperature Tolerance
Over Full Range ±1º F (±0.5º C)
At Room Temperatures ±1º F (+0.4/-0.2º C)
Setpoint Range
Heat Setpoint 38º to 89º F (3º to 32º C)
Cool Setpoint 59º to 99º F (15º to 37º C)
Relay Rating 1 amp @ 40 volts dc or 24 volts ac (nominal)
Environmental
Temperature -10º to 110º F (-23º to 43º C)
Humidity 10% to 90% RH (non-condensing)