Crestron CHV-TSTATEX-FCU infiNET EX Thermostat (Fan Coil Unit)
Operations & Installation Guide DOC. 7206C infiNET EX Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU
19
NOTE: While in Setup mode, a period of one minute with no button activity causes
the CHV-TSTATEX-FCU to revert to standard operation, unless a function (such as
an infiNET EX acquire) is executing.
Setup Mode Parameters/Functions
The following table shows the available setup parameters/functions.
Setup Mode Parameters/Functions
PARAMETER/
FUNCTION
CODE VALID VALUES
DEFAULT
VALUE
NOTES
Temperature
Scale
FC F, C F Sets units to use for temperature display
(Fahrenheit or Celsius)
Backlight
Timeout
bL 1 4 seconds or
disabled (--)
4 seconds Sets the number of seconds the backlight
remains lit after a button press
Auto Dead
Band
db 2 6 (for
Fahrenheit)
or 1 3 (for
Celsius)
2 Used to set minimum separation between
heat and cool setpoints (with dual
setpoints) or maximum drift before
system latches alternate mode (with
single setpoint)
Heat Setpoint
Limit
HL 5090 80 Sets the highest heat setpoint that is
allowed
Cool Setpoint
Limit
CL 5090 60 Sets the lowest cool setpoint that is
allowed
Temperature
Offset
to -9 to +9 (for
Fahrenheit)
or -5 to +5 (for
Celsius)
0 Permits recalibration of room temperature
sensor;
This is the number of degrees added to
or subtracted from the actual
temperature;
This adjustment changes the actual
regulation temperature, not just the
display
Heat Anticipator HA 1 – 6 3 Lower setting results in more frequent
cycles and faster response (tighter
regulation);
Higher setting results in less frequent
cycles and slower response (looser
regulation);
The default value should suffice in nearly
all installations
Cool Anticipator CA 1 – 6 3 Lower setting results in more frequent
cycles and faster response (tighter
regulation);
Higher setting results in less frequent
cycles and slower response (looser
regulation);
The default value should suffice in nearly
all installations
(Continued on following page)