Crestron CHV-TSTATEX-FCU Guia de Instalação Página 16

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 40
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 15
infiNET EX Thermostat (Fan Coil Unit) Crestron CHV-TSTATEX-FCU
12
infiNET EX Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU Operations & Installation Guide DOC. 7206C
NOTE: Steal Power mode may cause problems with some types of HVAC systems,
such as indicating a false heat or cool call. If this occurs, do not use Steal Power
mode.
If the thermostat will be wired so that 24 volts ac are always be present on the 24C
terminal, slide the POWER switch to 24VAC. No batteries are required in this
mode.
NOTE: When the unit detects 24 Vac, it no longer “sleeps, meaning it offers real-
time communication with the control system.
NOTE: When the unit is powered from a constant 24 Vac supply, there may be a
slight discrepancy between the ambient temperature displayed on the thermostat and
the actual room temperature. This discrepancy is also seen when switching from
STEAL to 24VAC. This is normal and the discrepancy disappears within
approximately 10 minutes.
Wiring the CHV-TSTATEX-FCU to the HVAC
System
Make the necessary connections as called out in the illustrations that follow. A flat
head screwdriver (not supplied) is required to attach the control wires from the
HVAC system. Apply power after all connections have been made.
The illustrations on the following pages show examples for connection to various
types of HVAC systems. If the system being connected does not match any of the
systems described below, contact Crestron Technical Support for assistance.