Crestron CHV-TSTATEX-FCU infiNET EX Thermostat (Fan Coil Unit)
Operations & Installation Guide – DOC. 7206C infiNET EX Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU
23
Operation
System Mode
The MODE button on the CHV-TSTATEX-FCU cycles the unit through all
available system modes in the following order: Off, Heat, Emergency Heat (for heat
pump and dual-fuel systems), Cool and Auto (if enabled in Setup).
The system mode changes upon release of the MODE button and the selected mode
becomes operational 5 seconds after the mode has been entered.
Off Mode
In Off mode, all HVAC systems are disabled.
Heat Mode
In Heat mode, the thermostat uses the heating system to maintain the setpoint
temperature.
Cool Mode
In Cool mode, the thermostat uses the cooling system to maintain the setpoint
temperature.
Auto Mode
In Auto mode, the thermostat allows the system to switch between Heat and Cool
automatically as needed to maintain the setpoint temperature. By default, the
CHV-TSTATEX-FCU has been configured with Auto mode disabled, meaning it is
not available from the thermostat itself or via another interface such as a touch
screen.
In order to enable Auto mode, enter Setup mode and change the AU setting from
“--” to either d (dual setpoint) or S (single setpoint). Refer to “Setup Mode” which
starts on page 18 for details.
Once Auto mode has been enabled, it can be accessed from the
CHV-TSTATEX-FCU controls as follows:
1. Press the MODE button until both the flame
and snowflake icons
appear in the display. This indicates Auto mode is now active.
2. Use the
and buttons to adjust the setpoint. Actual operation depends on
whether single or dual setpoints are being used.
a. In dual setpoint Auto mode, the first press of the
or buttons (or
second press if the first press simply turned on the backlight) causes
either the flame
or snowflake icon to flash rapidly. This
indicates which setpoint is adjusted by subsequent presses of the
or
buttons. To adjust or view the alternate setpoint, press the MODE
button while the icon is flashing. This causes the alternate icon to flash
and now the
and buttons adjust that setpoint. The flashing icon
times out after 5 seconds of no button activity.
b. In single setpoint Auto mode, use the buttons to adjust the setpoint as
usual.