230 V Lighting Design Guide
24
Doc. 4859C | crestron.com
Crestron Network Block (CAEN-BLOCK) provides four termination ports for Cresnet wiring. The unit also has two
5-pin connections that provide communication to the modules. The contact closure override signals that produce
an emergency override of the modules are also sent through these connections. The override connector provides
external dry contact closure inputs directly to the 5-position Cresnet interconnect connectors, LEFT and RIGHT.
When a switch contact closure is received between the G connections and the L or R connection (R is used in a
double-wide enclosure only) on the CAEN BLOCK, the respective left or right column of modules will set the lights to
the programmed emergency over-ride state. The override connector is rated at 5 volts, 10 mA maximum.
The CAEN-BLOCK unit is a pass-through device with a Cresnet power factor of zero.
CAEN-BLOCK
Network Block Dimensions and Weight
Height Width Depth Weight
5.08 cm 15.24 cm 4.45 cm 1.54 kg
CAEN-BLOCK Location and Orientation within a Single-Wide Enclosure