Crestron e-control Database Manager SW-DBM
86 Appendices Installation & Reference Guide — DOC. 5823
Requery scroller signal
Description
Causes server to respond by going back to the database to rebuild the current
scroller page, resends all scroller strings.
Direction
System to Server
Type
Digital
Value
Pulse
Expected Reply Possible Data signals (all with null values); followed by all in-use List signals
Comments
Despite its name, this signal does not actually re-run the query; it just moves
through the already-established recordset again to rebuild the current scroller
page, sending serial data back to the control system via the List signals. Note that
all these list signals are always transmitted because the proxies are also being
rebuilt.
If a record is opened when this signal is issued, it is closed. This action sends out
blanking Data signals.
This signal cannot be defined in an emailer scroller.
See Also List and Data signals