Hardware Hookup
CHV-RSS sensors connect to the terminal blocks on the back plate of the
CHV-TSTAT, CHV-THSTAT, CHV-TSTATEX, CHV-TSTATEX-FCU
thermostats (all sold separately).
NOTE: Sensor wiring is non-polarized.
NOTE: Up to two CHV-RSS sensors may be connected to a single
channel.
NOTE: Use a separate run of wire for each sensor.
NOTE: Wire runs should be low capacitance twisted pair wire such as
CAT3 (up to 250 feet (76 meters)), CAT5 (up to 500 feet (152 meters)),
or similar low capacitance (less than 7000 pF) wire.
NOTE: Sensor lines should not be run parallel to any other wiring. Lines
should cross other cables at right angles.
Complete the following procedure to connect the CHV-RSS to the
system:
1. Turn off the circuit breaker.
CAUTION: Do not press on the LCD display of the thermostat
during this procedure, as this may cause the screen to crack.
2. Separate thermostat front plate from back plate (it may be
necessary to exert force when removing the faceplate.)