Crestron Green Light DIN-HUB Guia de Instalação Página 15

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 36
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 14
Crestron DIN-IO8 DIN Rail Versiport Module
When the desired Net ID is displayed, press the SETUP button to
exit the Setup mode. The SETUP LED extinguishes.
NOTE: If an invalid Net ID is set (00, 02, FF), “Er” will be
displayed on the NET ID display. The DIN-IO8 reverts to the
previously set Net ID.
NOTE: The DIN-IO8 will leave the Setup mode after 10 seconds
of inactivity. The DIN-IO8 will revert to the previously set Net ID.
NOTE: A small label (with numbers and letters) is provided on
the front panel of the DIN-IO8 to document the unit’s Net ID in
the case where power is not available. Apply a mark over the digits
that correspond to the assigned Net ID.
NET ID Label (“3C” Shown)
When setting the Net ID, consider the following:
The Net ID of each unit must match an ID code specified in the
SIMPL™ Windows
®
program.
Each network device must have a unique Net ID.
For more details, refer to the Crestron Toolbox help file.
Installation
The DIN-IO8 must be installed by a licensed electrician, in accordance
with all national and local codes.
CAUTION: This equipment is for indoor use only. Mount in a well
ventilated area. The ambient temperature must be 0º to 40º C
(32º to 104º F). The relative humidity must be 10% – 90%
(non-condensing).
Operations & Installation Guide – DOC. 6664A DIN Rail Versiport Module: DIN-IO8 11
Vista de página 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20 ... 35 36

Comentários a estes Manuais

Sem comentários