CH-DIM4-D9 Product Manual
Crestron International • 2 Oude Keerbergsebaan • 2820 Rijmenam • Belgium
Tel: +32 15 50 99 50 • [email protected]www.crestron-int.be
3
Description
Figure 1: CH-DIM4-D9
Functional Description
The CH-DIM4-D9 is an analog output interface for control of fluorescent dimmable
ballasts. 4 Cut-off relay’s are implemented to cut the 230V feed to the load if the analog
output is <1VDC. This is to prevent the Fluorescent light from flickering (Figure 1).
4 analog outputs 0-10VDC or 1-10VDC for control of Electronic ballasts.
Each analog output can handle a max output current of 25mA; all 4 outputs together
maximum 100mA (per output +-/ 25 ballast’s).
Analog Outputs are each settable to Sink (1-10V) or Source (0-10V)
4 relays for Cut-off purpose to prevent the load of flickering, each rated
250VAC/16Amp (cut off value can be programmed).
Red led feedback per Cut-off relay.
1 override input (dry contact) or dipswitch that triggers all outputs to 10VDC for
testing or emergency reasons
Cresnet unit with rotary switches for NET-ID settings.
DIN rail mountable