iLux Dimmer Expansion Module Crestron CLS-EXP-DIMFLV
Installation Guide DOC. 6680B iLux 0-10V Fluorescent Dimmer Expansion Module: CLS-EXP-DIMFLV
5
Connectors and Indicators (Continued)
# CONNECTORS
AND
INDICATORS
DESCRIPTION
3 INPUTCTRL
(1) Captive screw terminal,
1
control input from
CLS(I)-C6 Series,
CLW-DIM Series,
2
CLX(I)-DIM Series,
GLX-DIM6, GLXX-2DIM8,
DIN-1DIM4, or
DIN-1DIMU4 dimmers
NOTE: Presents a 25 watt
load to the controlling
dimmer; a maximum of five
CLS-EXP-DIMFLV modules
may be connected to the
controlling dimmer, which
cannot be wired to control
any other loads besides the
CLS-EXP-DIMFLV
modules.
4 INPUTNEUT
(1) Captive screw terminal,
1
neutral connection for
control input
5 OUTPUTSW OUT
(1) Captive screw terminal,
1
switched load output
6 OUTPUTHOT
(1) Captive screw terminal,
1
line power input
7 OUTPUTNEUT
(1) Captive screw terminal,
1
neutral connection for line
power input and load
8 0-10V(+)
(1) Captive screw terminal,
1
dimming control output;
Class 1 or Class 2 wiring
allowed;
Control Voltage: 0-10 Vdc,
70 mA
9 0-10V–(-)
(1) Captive screw terminal,
1
dimming control output;
Class 1 or Class 2 wiring
allowed;
Control Voltage: 0-10 Vdc,
70 mA
10 GROUND
(1) 3-terminal chassis
ground bus bar
1. Captive screw terminals accept up to two 22 to 12 AWG (0.34 to
4 mm
2
) wires per terminal.
2. CLW-Series device must have a dedicated neutral.
Setup
Important Notes
Read before installation.
Install in accordance with all local and national
electrical codes.
Use 75°C copper wire only.
Installation
Refer to the following diagram when installing a
CLS-EXP-DIMFLV module.
Module Installation
NOTE: To prevent potential heat damage to the drywall,
do not mount the CLS-EXP-DIMFLV directly onto
drywall. Mount a piece of 1/2 in (13 mm) minimum thick
plywood between the CLS-EXP-DIMFLV and the
drywall.
NOTE: To ensure proper ventilation, the device must be
installed vertically on a vertical surface. Install device
with 6 inches (153 mm) of clearance from the top and
bottom of the device.
Mounting Surface
CLS-EXP-DIMFLV
Mounting Screw, #8
Qty. 4 Total
(Not Supplied)